wpe2.gif (2364 bytes)

           We Deliver Your Power Needs !

 

 

Home Up Contents

 

 Home
Up

 

KR-22010 Rectifier ModuleKR-22010-(low-resolution).gif (28314 bytes)

Topaz KR-22010 is 6U in height and 89mm wide, allowing 5 units across a 19 inch rack. It features unity power factor, typical efficiency greater than 90%, a wide AC input range of 150 - 275Vac with forced air cooling in an ambient of 0 - 50°C. Its hot-plug capability enables it to be safely taken in and out of the rack without switching off the power.

KR-22010 (220V/10A) Specification

Input
Voltage 150 to 275V, single phase
Active, Neutral, Earth
220 +25%-32% Vac
Frequency 45 to 65 Hz
Current 21 A rms max at 150 Vac.
14 A rms at 220 Vac
Power Factor >0.99 at full load
Sinusoidal waveform
THD<5% at full load
Efficiency >90% typical from 50 to 100% output at nominal input voltage
Protection HRC fuses at input of SMR
Power circuit is turned off if AC voltage >280 Vac or <145 Vac.
Surge Protection Tested to ANSI C62.41-1991, Cat. B3: high system exposure: Combination wave 6kV/3kA test
Ring wave 6kV/500A test
Voltage Withstand Test 1500 Vac input to chassis for 1 minute (2200 Vdc 100% testing on production units)
EMI CISPR22 Class B.
Inrush Current <8A peak at nominal mains voltage
Soft Start Time 8 secs min o/p current ramp-up
Output
Voltage Float: Adjustable 220 to 280V
Equalise: Adjustable 250 to 310V
Current Limit Adjustable 2 to 12A
Power Limit
(1680W output)
Max current limit 12A at 233Vdc, 11A at 254Vdc, 10A at 280Vdc, 9A at 310Vdc
Conversion Frequency 140 and 180 kHz
Static Regulation Line: ± 0.02%, Load: ± 0.05%
Dynamic Regulation ± 1% of final voltage for 10% to 90% to 10% step load change. ± 1% for ± 25% step change in AC input voltage.
Output Noise

< 20mV rms Psophometric weighting.

< 100mV rms 100Hz to 100MHz.

< 1V peak to peak 100MHz.

Load Sharing Better than ± 5% active current sharing at full load.
Protection Fuse at output of SMR.
Overvoltage Only faulty unit shuts down.
Overcurrent Can sustain short circuit at output terminals indefinitely.
Overtemperature Gradual reduction of current
Monitoring
Current Monitored on MiniCSU display. Accuracy ± 1% at full load. Optional bar-graph display.
Voltage System voltage displayed on MiniCSU's alpha-numeric display. Accuracy ± 0.5% at full load.
Alarms SMR normal, SMR alarm present and SMR shutdown indicated on front panel. Other alarms and status displayed on MiniCSU.
Remote Controls
Equalise Mode Equalise Mode is initiated by a signal from the MiniCSU.
External Voltage Control (EVC) Optically coupled PWM signal used to control rectifier Float and Equalise voltage over a limited range to optimally adjust battery voltage for temperature and voltage drop in DC bus, limit the maximum battery recharging current and achieve active current sharing. See MiniCSU specification.
Rectifier Inhibit Rectifier can be inhibited by a signal from a remote computer, transmitted via the MiniCSU.
Environmental
Cooling Forced air cooling. Fan speed control
Temperature Operating range: 0° to 50° C.
Humidity 0% to 90% non-condensing.
Mechanical
Noise < 55 dBA ( A Weighted).
Dimensions Height 267 mm (6 U).
Width 89 mm.
Depth 300 mm.
Mass < 6 kg.
Magazine Size The KR-Mag5 Magazine holds 5 Rectifiers across a 19" rack. One row of Rectifiers occupies 9U of rack height, 3U occupied by fan unit. The Magazine fits a rack depth of 400mm or greater.
Connections Input, Output & a multi-purpose connector is mounted on the back of the Rectifier Module with a matching connector at the back of the Magazine. Mating of connectors occurs when the Rectifier is plugged into the Magazine.The Rectifier is mechanically latched to ensure a reliable connection.
 

 

Send mail to info@topazpower.com with questions or comments about this web site.
Copyright © 1999 TOPAZ POWER (M) SDN BHD
Last modified: September 16, 2004