KR-48100 Rectifier Module

Topaz KR-48100 is a compact 2U high by 19 inch wide rectifier module and up to 20 units, equivalent to 2,000A can be can be constructed in a single rack. Power systems of up to 11,000A capacity can be constructed using multiple racks. It features unity power factor, typical efficiency greater than 91%, a wide AC input range of 187 - 275Vac with forced air cooling in an ambient of 0 - 50°C. KR-48100-(low-resolution).gif (21640 bytes)

KR-48100 (48V/100A) Specification

Input
Voltage

187 to 275V, single phase
Active, Neutral, Earth
220 +25%-15% Vac

Output power limit reduced if Vac is below 187V, at 150V 70% of output power available.

Frequency 45 to 65 Hz
Current 33 A rms max at 187 Vac.
28 A rms at 220 Vac
Power Factor >0.99 at full load
Sinusoidal waveform
THD<8% at full load
Complies with IEC555-2
Efficiency 91% typical at full load. >90% above 25 Adc.
Protection HRC fuses at input of SMR
Power circuit is turned off if AC voltage >275 Vac or <150 Vac.
Surge Protection Tested to ANSI C62.41-1991, Cat. B3: high system exposure: Combination wave 6kV/3kA test
Ring wave 6kV/500A test
Voltage Withstand Test 1500 Vac input to chassis for 1 minute (2200 Vdc 100% testing on production units)
EMI CISPR22 Class B
Inrush Current <9A peak
Soft Start Time 5 secs min o/p current ramp-up
Output
Voltage Float: Adjustable 48 to 58V
Equalise: Adjustable 50 to 60V
Current Limit Adjustable 5 to 102A
Power Limit
(1680W output)
Max current limit 102A at 51Vdc, 100A at 56 Vdc, 93A at 60 Vdc
Conversion Frequency >20 kHz
Static Regulation Line: ± 0.1%, Load: ± 0.5%
Dynamic Regulation

± 5% for 10% to 90% to 10% step load change.

± 1% for ± 25% step change in AC input voltage.

Output Noise

< 2mV rms Psophometric weighting.

< 10mV rms 10 kHz to 100MHz.

< 100mV peak to peak 100MHz.

Load Sharing Better than ± 3% active current sharing at full load.
Protection Fuse at output of SMR.
Overvoltage Only faulty unit shuts down.
Overcurrent Can sustain short circuit at output terminals indefinitely.
Overtemperature Gradual reduction of current limit
Monitoring
Current Normally displayed on alphanumeric LCD display. Accuracy ± 0.5% at full load.  
Voltage Normally displayed on alphanumeric LCD display. Accuracy ± 0.5% at full load.
Alarms AC on, SMR off and SMR alarm present indicated on front panel. Other alarms and status are displayed on the alphanumeric LCD display.
Remote Alarms All alarm states defined above are transmitted to the MiniCSU
Remote Controls
Equalise Mode Equalise Mode is initiated by a signal from the MiniCSU.
External Voltage Control (EVC) Optically coupled PWM signal used to control rectifier Float and Equalise voltage over a limited range to optimally adjust battery voltage for temperature and voltage drop in DC bus, limit the maximum battery recharging current and achieve active current sharing. See MiniCSU specification.
Rectifier Inhibit Rectifier can be inhibited by a signal from a remote computer, transmitted via the MiniCSU.
Environmental
Cooling Forced air cooling.
Temperature Operating range: 0° to 50° C.
Humidity 0% to 90% non-condensing.
Mechanical
Noise < 60 dBA ( A Weighted).
Dimensions Height 88 mm (2 U).
Width 434 mm.
Depth 430 mm.
Mass 17 kg.
Connections Connectors are backplane of unit. Matching connectors are located at the back of the magazine. Mating of connectors occurs when unit is plugged into magazine.
 

 